CFD optimization of return air ratio and use of upper room UVGI
in combined HVAC and heat recovery system
Abstract
Several strategies and techniques have been recently developed to decrease energy consumption in heating, ventilation, and air-conditioning
(HVAC) systems. One method is to recirculate a fraction of return air and make use of the remaining part (exhaust) to preheat fresh air in order
to reduce the heating load. However, limitations must be imposed to the return fraction to maintain acceptable indoor air quality (IAQ).
The aim of this paper is to develop a computational fluid dynamics (CFD) model to predict the dispersion of CO2 and airborne bacteria in all-air
HVAC systems with aforementioned heat recovery system for known return air ratios as well as the disinfection of indoor air by upper room Ultraviolet
Germicidal Irradiation (UVGI).
The developed model can be put to practical use for estimating the maximum allowable return that minimizes energy cost of the integrated
system while maintaining acceptable IAQ. It can also be used to predict the minimum required UV output to eliminate any excess in bacteria count
in the breathing zone without the need for additional fresh air intake at the supply.